External bypass G-H / divider

Product benefits
- Option for drainage of large areas in combination with traditional separator technology
Product information
- Shaft divides the required amount of water that goes into the separator and bypass line
- Product body made of glass reinforced plastic
- Pipe connection using suitable push sockets or pipe connectors (no welded sockets)
- Suitable top sections

Top sections reduced (600) for grease separators

Top sections reduced for light oil separators

Top sections for GRP sampling units

Sampling units for GRP separators
ACO Belt 75 SS
ACO Belt 120 SS
Alarm device (OB)
Alarm device (O)
Alarm device (B)
Alarm device (OB) + casing
Control unit GA 1 + one sensor GA - SG1
Suitable for
GA-1 is an alarm device specially designed for grease separators. They indicate when it is time to empty the grease separator and thus prevents harmful grease emissions to the sewer system.
Description
- Dimensions: 125 mm x 75 mm x 35 mm (L x H x D
- Material: Polycarbonate
- Enclosure: IP65
- Operation temperature: -30 °C...+50 °C
- Supply voltage: 230 VAC ± 10 %, 50/60 Hz
- The device is not equipped with a mains switch
- Power consumption: GA-1: 5 VA, GA-2: 5 VA
- Sensors: 1 or 2 GA-SG1 sensors
- Relay outputs: Potential-free relay output 250 V, 5 A
- 1 pcs for GA-1 Operational delay 10 sec. Relay de-energize
- 2 pcs for GA-2 at trigger point.
- Electrical safety: IEC/EN 61010-1, Class II , CAT II
- EMC: IEC/EN 61000-6-3 (Emission)
- IEC/EN 61000-6-1 (Immunity)
Control unit GA 2 + two senzors GA - SG1
Suitable for
GA-2 is an alarm device for monitoring the thickness of the grease layer accumulating in a grease interceptor and the blocking of the interceptor. The system consists of a GA-2 control unit, two GA-SG1 sensors and a cable joint.
Description
- Dimensions 125 mm x 75 mm x 35 mm (L x H x D)
- Package 1,2 kg (control unit + 2 sensors + cable joint)
- Enclosure IP 65, material polycarbonate
- Cable glands adjustment range 6-10 mm
- Operation temperature -30 ºC...+50 ºC
- Supply voltage 230 VAC ± 10 %, 50/60 Hz
- The device is not equipped with a mains switch
- Power consumption 5 VA
- Sensors 2 pcs GA-SG1 sensors
- Relay output 2 pcs potential-free relay outputs
- 250 V, 5 A Operational delay 10 sec.
- Relay de-energize at trigger point.
- Electrical safety IEC/EN 61010-1, Class II , CAT II
- EMC Emission IEC/EN 61000-6-3
- Immunity IEC/EN 61000-6-1